8 - 52 8 - 52
8 FUNCTIONS
8.3 Handy Functions
This section explains some handy functions of the L series master/local module.
8.3.1 Remote device station initialization procedure registration function
The initial settings of remote device stations can be performed using GX Works2 for
registration to the programmable controller CPU.
The L series master/local module instructs registration or remote device station
initialization procedure (SB000D) and then stores the number of the currently
executing procedure to the buffer memory. For this reason, when processing has
stopped, the relevant information such as the procedure number or target station
number can be confirmed. For details on procedure numbers, refer to (1)(b)(9) in
Section 8.3.1.
Also, if a running remote device station is replaced due to a failure, initial processing
that has been done for all stations before can be performed for the replaced remote
device station by specifying it. Remote device stations other than the specified station
continue to operate.
Settings such as "A-D conversion enable/disable" and "Averaging processing
specification" can be performed easily with the AJ65BT-64AD.
For the availability of this function, refer to the manuals of the remote device stations to
be used.
(1) Number of setting items for remote device station initialization
procedure registration
Remote device station initialization procedure registration can be executed up to
16 items per remote device station.
If setting 17 items or more is necessary, execute initial setting with the program.
The initial processing in the remote device station initialization procedure
registration and initial settings with the program cannot be executed at the same
time.
Executing them at the same time may cause remote device station malfunction.
Remote device station initialization procedure registration can be executed up to
16 stations.
When 17 or more remote device stations are connected, execute the initial
settings for the 17th and subsequent stations using the program.
Summary of Contents for L26CPU-BT
Page 1: ......
Page 2: ......
Page 32: ...3 5 3 5 3 SPECIFICATIONS ...
Page 51: ...4 2 4 2 4 PROCEDURE BEFORE OPERATION 4 ...
Page 61: ...6 4 6 4 6 INSTALLATION AND CONNECTION ...
Page 63: ...6 6 6 6 6 INSTALLATION AND CONNECTION 8 The connection method is shown below ...
Page 70: ...6 13 6 13 6 INSTALLATION AND CONNECTION ...
Page 72: ...6 15 6 15 6 INSTALLATION AND CONNECTION ...
Page 139: ...8 33 8 33 8 FUNCTIONS ...
Page 151: ...8 45 8 45 8 FUNCTIONS ...
Page 246: ...11 9 11 9 11 EXAMPLE OF COMMUNICATION BETWEEN THE MASTER STATION AND REMOTE DEVICE STATIONS ...
Page 311: ...13 2 13 2 13 COMMUNICATION BETWEEN THE MASTER STATION AND INTELLIGENT DEVICE STATIONS MEMO 13 ...
Page 321: ...14 10 14 10 14 EXAMPLE OF COMMUNICATION WHEN MOUNTING MODULES ON THE HEAD MODULE ...
Page 326: ...15 5 15 5 15 TROUBLESHOOTING To the next page ...
Page 327: ...15 6 15 6 15 TROUBLESHOOTING To the next page ...
Page 328: ...15 7 15 7 15 TROUBLESHOOTING ...
Page 329: ...15 8 15 8 15 TROUBLESHOOTING 2 Troubleshooting by status logging ...
Page 436: ...App 72 App 72 APPENDIXES 7 Operating procedure of the transmission speed test ...
Page 439: ...App 75 App 75 APPENDIXES MEMO ...
Page 447: ......
Page 448: ......
Page 449: ......