7 - 31 7 - 31
7 PARAMETER SETTINGS
Item Description
Master
station
Local
station
Standby
Master
station
Reference
Total Module Connected
Set the total number of connected stations in the CC-Link system including
reserved stations for "Total Module Connected".
Default value: 64 (modules)
Setting range: 1 to 64 (modules)
――
Remote Input (RX)
Set the remote input (RX) refresh device.
Default value: Blank
Setting range: Device name - Select from X, M, L, B, D, W, R or ZR.
Device number - Within the range of the device points that
the CPU has.
――
Remote Output (RY)
Set the remote output (RY) refresh device.
Default value: Blank
Setting range: Device name - Select from
Y, M, L, B, T, C, ST, D, W, R or ZR.
Device number - Within the range of the device points that
the CPU has.
――
Remote Register (RWr)
Set the remote register (RWr) refresh device.
Default value: Blank
Setting range: Device name - Select from M, L, B, D, W, R or ZR.
Device number - Within the range of the device points that
the CPU has.
――
Remote Register (RWw)
Set the remote register (RWw) refresh device.
Default value: Blank
Setting range: Device name - Select from
M, L, B, T, C, ST, D, W, R or ZR.
Device number - Within the range of the device points that
the CPU has.
――
Special Relay (SB)
Set the link special relay (SB) refresh device.
Default value: Blank
Setting range: Device name - Select from M, L, B, D, W, R, SB or ZR.
Device number - Within the range of the device points that
the CPU has.
――
Special Register (SW)
Set the link special register (SW) refresh device.
Default value: Blank
Setting range: Device name - Select from M, L, B, D, W, R, SW or ZR.
Device number - Within the range of the device points that
the CPU has.
――
PLC Down Select
Set the data link status when a master station programmable controller
CPU error occurs.
Default value: Stop
Setting range: Stop
Continue
Section
8.2.3,
Section
8.2.6
Scan Mode Setting
Set whether the link scan for the sequence scan is synchronous or
asynchronous.
Default value: Asynchronous
Setting range: Asynchronous
Synchronous
Section
8.3.7
: Available, : Not available
Summary of Contents for L26CPU-BT
Page 1: ......
Page 2: ......
Page 32: ...3 5 3 5 3 SPECIFICATIONS ...
Page 51: ...4 2 4 2 4 PROCEDURE BEFORE OPERATION 4 ...
Page 61: ...6 4 6 4 6 INSTALLATION AND CONNECTION ...
Page 63: ...6 6 6 6 6 INSTALLATION AND CONNECTION 8 The connection method is shown below ...
Page 70: ...6 13 6 13 6 INSTALLATION AND CONNECTION ...
Page 72: ...6 15 6 15 6 INSTALLATION AND CONNECTION ...
Page 139: ...8 33 8 33 8 FUNCTIONS ...
Page 151: ...8 45 8 45 8 FUNCTIONS ...
Page 246: ...11 9 11 9 11 EXAMPLE OF COMMUNICATION BETWEEN THE MASTER STATION AND REMOTE DEVICE STATIONS ...
Page 311: ...13 2 13 2 13 COMMUNICATION BETWEEN THE MASTER STATION AND INTELLIGENT DEVICE STATIONS MEMO 13 ...
Page 321: ...14 10 14 10 14 EXAMPLE OF COMMUNICATION WHEN MOUNTING MODULES ON THE HEAD MODULE ...
Page 326: ...15 5 15 5 15 TROUBLESHOOTING To the next page ...
Page 327: ...15 6 15 6 15 TROUBLESHOOTING To the next page ...
Page 328: ...15 7 15 7 15 TROUBLESHOOTING ...
Page 329: ...15 8 15 8 15 TROUBLESHOOTING 2 Troubleshooting by status logging ...
Page 436: ...App 72 App 72 APPENDIXES 7 Operating procedure of the transmission speed test ...
Page 439: ...App 75 App 75 APPENDIXES MEMO ...
Page 447: ......
Page 448: ......
Page 449: ......