15 - 28 15 - 28
15 TROUBLESHOOTING
Detectability
Error code
(hexadecimal)
Error details
Cause of error occurrence (details)
Corrective action
Master station
Local station
B3A5
Mode invalid (parameter)
The mode set in the control data of the
G(P).RLPASET instruction differs from
the mode set with switch 3 of the
intelligent module switch setting.
Check the control data of the
G(P).RLPASET instruction and
the switch 3 setting of the
intelligent module switch
setting.
B401
Parameter change error
Parameter change was executed during
transient request.
Change the parameter after all
transient requests are
completed or before any are
requested.
B404 Response
error
A response from the requested station
was not returned within the watchdog
time period.
Set a longer watchdog time. If
an error persists, check the
requested module and cables.
B405
Transient applicable station
error
A transient request was made to a
remote I/O station or a remote device
station.
Set the corresponding station to
a local station or an intelligent
device station.
B410
Receive buffer size error
The receive buffer size of the dedicated
instruction is less than the response data
size.
Check the receive buffer size.
B411
Data length outside of range
The number of read/write points in the
control data of the dedicated instruction
is outside the setting range.
Change the number of
read/write points to within the
setting range.
B412
Station number outside of
range
The station number in the control data of
the dedicated instruction is outside the
setting range.
Change the station number to
within the setting range.
B413 Request
error
Multiple dedicated instructions were
executed for the same station.
Check the program.
B414
Interlock signal data outside of
range
The setting of the interlock signal storage
device of the G(P).RIRCV or
G(P).RISEND instruction is outside the
setting range.
Change the setting of the
interlock signal storage device
to within the setting range.
B418
Received data size error
Data exceeding the receivable data size
were received with the message
transmission function.
Set a value of the received data
size or more for the receivable
data size.
B601
Request type error
An unsupported request was received.
Check the contents of the
request, as well as the target
station number.
B602
Transient request overload
error
There are too many transient requests to
the corresponding station.
Wait a while and then send the
requests (transient overload
status).
B603
Transient request overload
error
There are too many transient requests to
the corresponding station.
Wait a while and then send the
requests (transient overload
status).
B604
Loop test in processing
Transient transmission was sent when a
loop test was in progress.
Wait a while and then
retransmit.
B605
Transient storage buffer could
not be obtained
Transient storage buffer could not be
obtained.
Wait a while and then
retransmit.
B607
Target station CPU error
There is an error in the target station's
CPU.
Check the target CPU.
B771
Transient request overload
error
There are too many transient requests to
the corresponding station.
Wait a while and then
retransmit (transient overloaded
status).
B774
Transient request error
The target station was not an intelligent
device station.
Check if the target station is an
intelligent device station.
B778 Response
time
out
A response was not received from the
requested station.
Check the requested module
and cables.
B780
Module mode setting error
A transient transmission was executed
even though the target station was set to
the I/O mode.
Set to the remote net mode.
B782
Station number specification
error
The transmission destination and source
stations were the same when other
station connection was specified.
Check the transmission
destination station number, or
change to host connection.
B783
Transient storage buffer error
An error occurred in the transient storage
buffer when a transient transmission of
greater than 1 k was being performed.
Wait a while and then
retransmit.
B801
Access code setting error
A non-existing access code/attribute was
set.
Set a correct access
code/attribute.
B802
Access code error
An access code that does not exist was
used.
Use the correct access code.
(To the next page)
Summary of Contents for L26CPU-BT
Page 1: ......
Page 2: ......
Page 32: ...3 5 3 5 3 SPECIFICATIONS ...
Page 51: ...4 2 4 2 4 PROCEDURE BEFORE OPERATION 4 ...
Page 61: ...6 4 6 4 6 INSTALLATION AND CONNECTION ...
Page 63: ...6 6 6 6 6 INSTALLATION AND CONNECTION 8 The connection method is shown below ...
Page 70: ...6 13 6 13 6 INSTALLATION AND CONNECTION ...
Page 72: ...6 15 6 15 6 INSTALLATION AND CONNECTION ...
Page 139: ...8 33 8 33 8 FUNCTIONS ...
Page 151: ...8 45 8 45 8 FUNCTIONS ...
Page 246: ...11 9 11 9 11 EXAMPLE OF COMMUNICATION BETWEEN THE MASTER STATION AND REMOTE DEVICE STATIONS ...
Page 311: ...13 2 13 2 13 COMMUNICATION BETWEEN THE MASTER STATION AND INTELLIGENT DEVICE STATIONS MEMO 13 ...
Page 321: ...14 10 14 10 14 EXAMPLE OF COMMUNICATION WHEN MOUNTING MODULES ON THE HEAD MODULE ...
Page 326: ...15 5 15 5 15 TROUBLESHOOTING To the next page ...
Page 327: ...15 6 15 6 15 TROUBLESHOOTING To the next page ...
Page 328: ...15 7 15 7 15 TROUBLESHOOTING ...
Page 329: ...15 8 15 8 15 TROUBLESHOOTING 2 Troubleshooting by status logging ...
Page 436: ...App 72 App 72 APPENDIXES 7 Operating procedure of the transmission speed test ...
Page 439: ...App 75 App 75 APPENDIXES MEMO ...
Page 447: ......
Page 448: ......
Page 449: ......