8 - 75 8 - 75
8 FUNCTIONS
8.3.9 Remote I/O station points setting
The points of each remote I/O station can be set to 8, 16 or 32 points.
This saves the refresh device points of the programmable controller CPU and link
refresh time.
The remote I/O station points setting can be used in the remote net ver. 2 mode only.
For parameter setting, use GX Works2.
This function cannot be executed if the dedicated instruction is used for parameter
setting. This function can be executed when read/write from/to the CPU devices is
performed according to the I/O points of each station at cyclic data refresh using the
FROM/TO instruction.
Y
Station
number 2
Remote output RY
Y07 to Y00
Y07 to Y00
Y0F to Y00
Y0F to Y00
Y1F to Y10
8-point output module
Device area when remote I/O points setting is made
Device area when remote I/O points setting is not made
8-point output module
16-point output module
32-point output module
Programmable
controller CPU
Master station
Station number 3
Station
number 4
to
Station
number 1
Remote I/O station
(Station number 1:
Occupies 1 station)
Remote I/O station
(Station number 2:
Occupies 1 station)
Remote I/O station
(Station number 3:
Occupies 1 station)
Remote I/O station
(Station number 4:
Occupies 1 station)
POINT
Set points to even-numbered 8-point setting remote I/O stations consecutively. If
points are set to odd-numbered 8-point setting remote stations, select 8 8
points reserved in the "Remote Station Points" setting of the last of the consecutive
remote I/O stations.
Remote output RY
8-point output module
Master station
to
Remote I/O station
(Station number 1:
Occupies 1 station)
Station
number 2
8points
(reserved)
Remote I/O station
(Station number 2:
Occupies 1 station)
Remote I/O station
(Station number 3:
Occupies 1 station)
Remote I/O station
(Station number 4:
Occupies 1 station)
8-point output module
8-point output module
32-point output module
Y0F to Y00
Y1F to Y10
Y07 to Y00
Y07 to Y00
Y07 to Y00
Station
number 1
Station
number 3
reserved
Station
number 4
Odd-numbered 8-point setting remote stations cannot be set for 8 remote station
points.
Remote output RY
8-point output module
Master station
to
Remote I/O station
(Station number 1:
Occupies 1 station)
Station
number 2
Cannot be set.
Remote I/O station
(Station number 2:
Occupies 1 station)
Remote I/O station
(Station number 3:
Occupies 1 station)
Remote I/O station
(Station number 4:
Occupies 1 station)
8-point output module
8-point output module
32-point output module
Y0F to Y00
Y1F to Y10
Y07 to Y00
Y07 to Y00
Y07 to Y00
Station
number 1
Station
number 3
Station number 4
Refer to Section 7.3 for parameter setting.
Summary of Contents for L26CPU-BT
Page 1: ......
Page 2: ......
Page 32: ...3 5 3 5 3 SPECIFICATIONS ...
Page 51: ...4 2 4 2 4 PROCEDURE BEFORE OPERATION 4 ...
Page 61: ...6 4 6 4 6 INSTALLATION AND CONNECTION ...
Page 63: ...6 6 6 6 6 INSTALLATION AND CONNECTION 8 The connection method is shown below ...
Page 70: ...6 13 6 13 6 INSTALLATION AND CONNECTION ...
Page 72: ...6 15 6 15 6 INSTALLATION AND CONNECTION ...
Page 139: ...8 33 8 33 8 FUNCTIONS ...
Page 151: ...8 45 8 45 8 FUNCTIONS ...
Page 246: ...11 9 11 9 11 EXAMPLE OF COMMUNICATION BETWEEN THE MASTER STATION AND REMOTE DEVICE STATIONS ...
Page 311: ...13 2 13 2 13 COMMUNICATION BETWEEN THE MASTER STATION AND INTELLIGENT DEVICE STATIONS MEMO 13 ...
Page 321: ...14 10 14 10 14 EXAMPLE OF COMMUNICATION WHEN MOUNTING MODULES ON THE HEAD MODULE ...
Page 326: ...15 5 15 5 15 TROUBLESHOOTING To the next page ...
Page 327: ...15 6 15 6 15 TROUBLESHOOTING To the next page ...
Page 328: ...15 7 15 7 15 TROUBLESHOOTING ...
Page 329: ...15 8 15 8 15 TROUBLESHOOTING 2 Troubleshooting by status logging ...
Page 436: ...App 72 App 72 APPENDIXES 7 Operating procedure of the transmission speed test ...
Page 439: ...App 75 App 75 APPENDIXES MEMO ...
Page 447: ......
Page 448: ......
Page 449: ......