3 - 2 3 - 2
3 SPECIFICATIONS
(1) Number of link points in remote net ver.2 mode or remote net
additional mode
Item Specifications
Maximum No. of link points per system
Remote I/O (RX/RY) : 8192 points
Remote register (RWw) : 2048 points (master station remote device
station/local station/intelligent device
station/standby master station)
Remote register (RWr) : 2048 points (remote device station/local
station/intelligent device station/standby
master station master station)
Expanded cyclic setting
Single
Double
Quadruple
Octuple
Remote I/O (RX/RY)
32 points
(30 points
for local
station)
32 points
(30 points
for local
station)
64 points
(62 points
for local
station)
128 points
(126 points
for local
station)
Remote register (RWw)
4 points
8 points
16 points
32 points
No. of link
points per
station
Remote register (RWr)
4 points
8 points
16 points
32 points
Remote I/O
(RX/RY)
32 points
32 points
64 points
128 points
Remote
register (RWw)
4 points
8 points
16 points
32 points
Occupies
1 station
Remote
register (RWr)
4 points
8 points
16 points
32 points
Remote I/O
(RX/RY)
64 points
96 points
192 points
384 points
Remote
register (RWw)
8 points
16 points
32 points
64 points
Occupies
2 stations
Remote
register (RWr)
8 points
16 points
32 points
64 points
Remote I/O
(RX/RY)
96 points
160 points
320 points
640 points
Remote
register (RWw)
12 points
24 points
48 points
96 points
Occupies
3 stations
Remote
register (RWr)
12 points
24 points
48 points
96 points
Remote I/O
(RX/RY)
128 points
224 points
448 points
896 points
Remote
register (RWw)
16 points
32 points
64 points
128 points
Number
of link
points per
number of
occupied
stations
Occupies
4 stations
Remote
register (RWr)
16 points
32 points
64 points
128 points
3
Summary of Contents for L26CPU-BT
Page 1: ......
Page 2: ......
Page 32: ...3 5 3 5 3 SPECIFICATIONS ...
Page 51: ...4 2 4 2 4 PROCEDURE BEFORE OPERATION 4 ...
Page 61: ...6 4 6 4 6 INSTALLATION AND CONNECTION ...
Page 63: ...6 6 6 6 6 INSTALLATION AND CONNECTION 8 The connection method is shown below ...
Page 70: ...6 13 6 13 6 INSTALLATION AND CONNECTION ...
Page 72: ...6 15 6 15 6 INSTALLATION AND CONNECTION ...
Page 139: ...8 33 8 33 8 FUNCTIONS ...
Page 151: ...8 45 8 45 8 FUNCTIONS ...
Page 246: ...11 9 11 9 11 EXAMPLE OF COMMUNICATION BETWEEN THE MASTER STATION AND REMOTE DEVICE STATIONS ...
Page 311: ...13 2 13 2 13 COMMUNICATION BETWEEN THE MASTER STATION AND INTELLIGENT DEVICE STATIONS MEMO 13 ...
Page 321: ...14 10 14 10 14 EXAMPLE OF COMMUNICATION WHEN MOUNTING MODULES ON THE HEAD MODULE ...
Page 326: ...15 5 15 5 15 TROUBLESHOOTING To the next page ...
Page 327: ...15 6 15 6 15 TROUBLESHOOTING To the next page ...
Page 328: ...15 7 15 7 15 TROUBLESHOOTING ...
Page 329: ...15 8 15 8 15 TROUBLESHOOTING 2 Troubleshooting by status logging ...
Page 436: ...App 72 App 72 APPENDIXES 7 Operating procedure of the transmission speed test ...
Page 439: ...App 75 App 75 APPENDIXES MEMO ...
Page 447: ......
Page 448: ......
Page 449: ......