Dancer feedback speed control details
87
3
472
R121
Second PID differential time
for values below set point
9999
0.01 to 10 s
Set the second PID differential time for values below set
point.
9999
As set in
Pr.469
.
473
R122
Third PID proportional band
9999
0.1 to 1000%
Set the third PID proportional band.
9999
As set in
Pr.129
/
Pr.464
.
474
R123
Third PID integral time
9999
0.1 to 3600 s
Set the third PID integral time.
9999
As set in
Pr.130
/
Pr.465
.
475
R124
Third PID differential time
9999
0.01 to 10 s
Set the third PID differential time.
9999
As set in
Pr.134
/
Pr.466
.
476
R125
Third PID proportional band
for values below set point
9999
0.1 to 1000%
Set the third PID proportional band for values below set
point.
9999
As set in
Pr.473
.
477
R126
Third PID integral time for
values below set point
9999
0.1 to 3600 s
Set the third PID integral time for values below set
point.
9999
As set in
Pr.474
.
478
R127
Third PID differential time for
values below set point
9999
0.01 to 10 s
Set the third PID differential time for values below set
point.
9999
As set in
Pr.475
.
479
R128
Fourth PID proportional band
9999
0.1 to 1000%
Set the fourth PID proportional band.
9999
As set in
Pr.129
/
Pr.464
.
480
R129
Fourth PID integral time
9999
0.1 to 3600 s
Set the fourth PID integral time.
9999
As set in
Pr.130
/
Pr.465
.
481
R130
Fourth PID differential time
9999
0.01 to 10 s
Set the fourth PID differential time.
9999
As set in
Pr.134
/
Pr.466
.
482
R131
Fourth PID proportional band
for values below set point
9999
0.1 to 1000%
Set the fourth PID proportional band for values below
set point.
9999
As set in
Pr.479
.
483
R132
Fourth PID integral time for
values below set point
9999
0.1 to 3600 s
Set the fourth PID integral time for values below set
point.
9999
As set in
Pr.480
.
484
R133
Fourth PID differential time
for values below set point
9999
0.01 to 10 s
Set the fourth PID differential time for values below set
point.
9999
As set in
Pr.481
.
486
R140
Deviation A
600%
400.1 to 600% Set the deviation used for selecting PID gain A.
487
R141
Deviation B
400%
400 to 599.9% Set the deviation used for selecting PID gain B.
488
R142
Deviation C1
9999
400.1 to
599.9%
Set the deviation used for selecting PID gain C1.
9999
The PID gain is 100%.
489
R143
Deviation C2
9999
400.1 to
599.9%
Set the deviation used for selecting PID gain C2.
9999
The PID gain is 100%.
490
R144
PID gain A
9999
0.1 to 1000%
Set the gain for the deviation A.
9999
The PID gain is 100%.
491
R145
PID gain B
9999
0.1 to 1000%
Set the gain for the deviation B.
9999
The PID gain is 100%.
492
R146
PID gain C1
9999
0.1 to 1000%
Set the gain for the deviation C1.
9999
The PID gain is 100%.
493
R147
PID gain C2
9999
0.1 to 1000%
Set the gain for the deviation C2.
9999
The PID gain is 100%.
494
R148
PID gain D
9999
0.1 to 1000%
Set the gain for the deviation in the C1 to C2 range.
9999
The PID gain is 100%.
Pr.
Name
Initial value
Setting
range
Description