Parameter list (by parameter number)
22
774
M101
Operation panel monitor
selection 1
1 to 3, 5 to 14, 17 to 20, 22
to 36, 38, 40 to 46, 50 to
57, 61 to 64, 67, 71 to 74,
81 to 93, 97, 98, 100,
9999
1
9999
775
M102
Operation panel monitor
selection 2
1
9999
776
M103
Operation panel monitor
selection 3
1
9999
778
A682
4 mA input check filter
0 to 10 s
0.01 s
0 s
T054
799
M520
Pulse increment setting for
output power
0.1, 1, 10, 100, 1000 kWh
0.1 kWh
1 kWh
800
G200
Control method selection
0 to 2, 9 to 12, 20,
100 to 102, 109 to 112
1
20
801
H704
Output limit level
0 to 400%, 9999
0.1%
9999
802
G102
Pre-excitation selection
0, 1
1
0
803
G210
Constant output range torque
characteristic selection
0 to 2, 10, 11
1
0
804
R300
Tension / Torque command
source selection
0 to 6
1
0
D400
805
D401
Torque command value (RAM)
600 to 1400%
1%
1000%
806
D402
Torque command value
(RAM,EEPROM)
600 to 1400%
1%
1000%
807
H410
Speed limit selection
0 to 2
1
0
808
H411
Forward rotation speed limit/
speed limit
0 to 400 Hz
0.01 Hz
60 Hz
50 Hz
809
H412
Reverse rotation speed limit/
reverse-side speed limit
0 to 400 Hz, 9999
0.01 Hz
9999
810
H700
Torque limit input method
selection
0 to 2
1
0
811
D030
Set resolution switchover
0, 1, 10, 11
1
0
812
H701
Torque limit level (regeneration)
0 to 400%, 9999
0.1%
9999
813
H702
Torque limit level (3rd quadrant)
0 to 400%, 9999
0.1%
9999
814
H703
Torque limit level (4th quadrant)
0 to 400%, 9999
0.1%
9999
815
H710
Torque limit level 2
0 to 400%, 9999
0.1%
9999
816
H720
Torque limit level during
acceleration
0 to 400%, 9999
0.1%
9999
817
H721
Torque limit level during
deceleration
0 to 400%, 9999
0.1%
9999
818
C112
Easy gain tuning response level
setting
1 to 15
1
2
819
C113
Easy gain tuning selection
0 to 2
1
0
820
G211
Speed control P gain 1
0 to 1000%
1%
60%
821
G212
Speed control integral time 1
0 to 20 s
0.001 s
0.333 s
822
T003
Speed setting filter 1
0 to 5 s, 9999
0.001 s
9999
823
G215
Speed detection filter 1
0 to 0.1 s
0.001 s
0.001 s
824
G213
Torque control P gain 1 (current
loop proportional gain)
0 to 500%
1%
100%
825
G214
Torque control integral time 1
(current loop integral time)
0 to 500 ms
0.1 ms
5 ms
826
T004
Torque setting filter 1
0 to 5 s, 9999
0.001 s
9999
827
G216
Torque detection filter 1
0 to 0.1 s
0.001 s
0 s
828
G224
Model speed control gain
0 to 1000%
1%
60%
829
R504
Taper ratio setting input filter
time constant
0 to 5 s
0.01 s
0.02 s
830
G311
Speed control P gain 2
0 to 1000%, 9999
1%
9999
831
G312
Speed control integral time 2
0 to 20 s, 9999
0.001 s
9999
832
T005
Speed setting filter 2
0 to 5 s, 9999
0.001 s
9999
833
G315
Speed detection filter 2
0 to 0.1 s, 9999
0.001 s
9999
834
G313
Torque control P gain 2
0 to 500%, 9999
1%
9999
835
G314
Torque control integral time 2
0 to 500 ms, 9999
0.1 ms
9999
836
T006
Torque setting filter 2
0 to 5 s, 9999
0.001 s
9999
837
G316
Torque detection filter 2
0 to 0.1 s, 9999
0.001 s
9999
840
G230
Torque bias selection
0 to 3, 24, 25, 9999
1
9999
841
G231
Torque bias 1
600 to 1400%, 9999
1%
9999
Pr.
Pr.
group
Name
Setting range
Minimum
setting
increments
Initial value Refer
to
page
Customer
setting
FM
CA
Summary of Contents for A800 Plus Series