Parameter list (by parameter number)
19
2
475
R124
Third PID differential time
0.01 to 10 s, 9999
0.01 s
9999
476
R125
Third PID proportional band for
values below set point
0.1 to 1000%, 9999
0.1%
9999
477
R126
Third PID integral time for
values below set point
0.1 to 3600 s, 9999
0.1 s
9999
478
R127
Third PID differential time for
values below set point
0.01 to 10 s, 9999
0.01 s
9999
479
R128
Fourth PID proportional band
0.1 to 1000%, 9999
0.1%
9999
480
R129
Fourth PID integral time
0.1 to 3600 s, 9999
0.1 s
9999
481
R130
Fourth PID differential time
0.01 to 10 s, 9999
0.01 s
9999
482
R131
Fourth PID proportional band for
values below set point
0.1 to 1000%, 9999
0.1%
9999
483
R132
Fourth PID integral time for
values below set point
0.1 to 3600 s, 9999
0.1 s
9999
484
R133
Fourth PID differential time for
values below set point
0.01 to 10 s, 9999
0.01 s
9999
485
R149
Integral control activation
0 to 3
1
0
486
R140
Deviation A
400.1 to 600%
0.1%
600%
487
R141
Deviation B
400 to 599.9%
0.1%
400%
488
R142
Deviation C1
400.1 to 599.9%, 9999
0.1%
9999
489
R143
Deviation C2
400.1 to 599.9%, 9999
0.1%
9999
490
R144
PID gain A
0.1 to 1000%, 9999
0.1%
9999
491
R145
PID gain B
0.1 to 1000%, 9999
0.1%
9999
492
R146
PID gain C1
0.1 to 1000%, 9999
0.1%
9999
493
R147
PID gain C2
0.1 to 1000%, 9999
0.1%
9999
494
R148
PID gain D
0.1 to 1000%, 9999
0.1%
9999
495
M500
Remote output selection
0, 1, 10, 11
1
0
─
496
M501
Remote output data 1
0 to 4095
1
0
─
497
M502
Remote output data 2
0 to 4095
1
0
─
498
A804
PLC function flash memory
clear
0, 9696 (0 to 9999)
1
0
─
502
N013
Stop mode selection at
communication error
0 to 2, 11, 12
1
0
─
503
E710
Maintenance timer 1
0 (1 to 9998)
1
0
─
504
E711
Maintenance timer 1 warning
output set time
0 to 9998, 9999
1
9999
─
505
M001
Speed setting reference
1 to 590 Hz
0.01 Hz
60 Hz
50 Hz
─
516
F400
S-pattern time at a start of
acceleration
0.1 to 2.5 s
0.1 s
0.1 s
─
517
F401
S-pattern time at a completion of
acceleration
0.1 to 2.5 s
0.1 s
0.1 s
─
518
F402
S-pattern time at a start of
deceleration
0.1 to 2.5 s
0.1 s
0.1 s
─
519
F403
S-pattern time at a completion of
deceleration
0.1 to 2.5 s
0.1 s
0.1 s
─
539
N002
MODBUS RTU communication
check time interval
0 to 999.8 s, 9999
0.1 s
9999
─
547
N040
USB communication station
number
0 to 31
1
0
─
548
N041
USB communication check time
interval
0 to 999.8 s, 9999
0.1 s
9999
─
549
N000
Protocol selection
0, 1
1
0
─
550
D012
NET mode operation command
source selection
0, 1, 9999
1
9999
─
551
D013
PU mode operation command
source selection
1 to 3, 9999
1
9999
─
552
H429
Frequency jump range
0 to 30 Hz, 9999
0.01 Hz
9999
─
553
A603
PID deviation limit
0.0 to 100.0%, 9999
0.1%
9999
─
554
A604
PID signal operation selection
0 to 3
1
0
555
E720
Current average time
0.1 to 1 s
0.1 s
1 s
─
556
E721
Data output mask time
0 to 20 s
0.1 s
0 s
─
557
E722
Current average value monitor
signal output reference current
0 to 500 A
Inverter rated
current
─
560
A712
Second frequency search gain
0 to 32767, 9999
1
9999
─
561
H020
PTC thermistor protection level
0.5 to 30 k
Ω
, 9999
0.01 k
Ω
9999
─
Pr.
Pr.
group
Name
Setting range
Minimum
setting
increments
Initial value Refer
to
page
Customer
setting
FM
CA