Parameter list (by parameter number)
20
563
M021
Energization time carrying-over
times
(0 to 65535)
1
0
564
M031
Operating time carrying-over
times
(0 to 65535)
1
0
565
G301
Second motor excitation current
break point
0 to 400 Hz, 9999
0.01 Hz
9999
566
G302
Second motor excitation current
low-speed scaling factor
0 to 300%, 9999
0.1%
9999
569
G942
Second motor speed control
gain
0 to 200%, 9999
0.1%
9999
570
E301
Multiple rating setting
0 to 3, 12
1
2
571
F103
Holding time at a start
0 to 10 s, 9999
0.1 s
9999
573
A680
4 mA input check selection
1 to 3, 9999
1
9999
T052
574
C211
Second motor online auto
tuning
0, 1
1
0
598
H102
Undervoltage level
350 to 430 V, 9999
0.1 V
9999
599
T721
X10 terminal input selection
0, 1
1
0
1
600
H001
First free thermal reduction
frequency 1
0 to 590 Hz, 9999
0.01 Hz
9999
601
H002
First free thermal reduction ratio 1
1 to 100%
1%
100%
602
H003
First free thermal reduction
frequency 2
0 to 590 Hz, 9999
0.01 Hz
9999
603
H004
First free thermal reduction ratio 2
1 to 100%
1%
100%
604
H005
First free thermal reduction
frequency 3
0 to 590 Hz, 9999
0.01 Hz
9999
606
T722
Power failure stop external
signal input selection
0, 1
1
1
607
H006
Motor permissible load level
110 to 250%
1%
150%
608
H016
Second motor permissible load
level
110 to 250%, 9999
1%
9999
611
F003
Acceleration time at a restart
0 to 3600 s, 9999
0.1 s
9999
617
G080
Reverse rotation excitation
current low-speed scaling factor
0 to 300%, 9999
0.1%
9999
620
R570
Line speed bias for reel change
0 to 2000 m/min
0.1 m/min
1000 m/min
621
R423
Allowable deviation from target
line speed
0 to 6553.4 m/min
0.1 m/min
0 m/min
,
622
R204
Line speed command for
starting
0 to 6553.4 m/min
0.1 m/min
0 m/min
635
R214
Line speed command added
compensation value voltage/
current bias
0 to 100%, 9999
0.1%
9999
636
R215
Line speed command added
compensation value bias
0 to 6553.4 m/min
,
9999
0.1 m/min
9999
637
R216
Line speed command added
compensation value voltage/
current gain
0 to 100%, 9999
0.1%
9999
638
R217
Line speed command added
compensation value gain
0 to 6553.4 m/min
,
9999
0.1 m/min
9999
639
R030
Speed control proportional term
applied diameter 1
1 to 99%, 9999
1%
9999
640
R031
Speed control proportional term
applied diameter 2
1 to 99%, 9999
1%
9999
641
R032
Speed control proportional gain 1
0 to 1000%, 9999
1%
9999
642
R033
Speed control proportional gain 2
0 to 1000%, 9999
1%
9999
643
R034
Speed control proportional gain 3
0 to 1000%, 9999
1%
9999
644
R035
Speed control proportional gain 4
0 to 1000%, 9999
1%
9999
645
R004
Winding diameter storage
selection
0, 1
1
0
646
R003
Stored winding diameter
1 to 6553 mm
1 mm
1 mm
647
R041
Operation time with stored
winding diameter
0 to 100 s
0.01 s
0 s
648
R420
Target winding diameter
1 to 6553 mm
1 mm
1 mm
650
R270
Terminal 4 input compensation
selection
0, 1
1
0
Pr.
Pr.
group
Name
Setting range
Minimum
setting
increments
Initial value Refer
to
page
Customer
setting
FM
CA
Summary of Contents for A800 Plus Series
Page 240: ...239 MEMO ...