Tension sensor feedback speed control details
106
TENSION SENSOR FEEDBACK SPEED CONTROL
4.5.1
Tension feedback setting
Set the target position for tension feedback.
Select the input method to the inverter (analog input terminal) for tension feedback input.
PID set point (Pr.133)
• Set the set point for tension feedback in
Pr.133 PID action set point
.
• Set a value according to the full scale value of the tension detector to be used and the corresponding output voltage. For
example, when tension feedback is input through terminal 1 and the tension sensor outputs 10 V for 100 N (full scale
value), set 530% in
Pr.133
to set 30 N tension.
NOTE
• Set
Pr.52
= "86" to monitor the tension feedback value on a percentage basis.
Tension feedback input selection (Pr.363)
• Use
Pr.363 Dancer / tension sensor feedback input selection
to select the input terminal for tension feedback.
∗1
The input specification in the initial setting is indicated.
Pr.
Name
Initial value
Setting range
Description
133
R101
(A611)
PID action set point
500%
400 to 600%
Set the set point for tension feedback.
363
R102
Dancer / tension sensor
feedback input selection
9999
3
The measured value is input through terminal 2.
4
The measured value is input through terminal 4.
5
The measured value is input through terminal 1.
6
The measured value is input through terminal 6
(FR-A8AZ).
9999
No function
1227
R103
Dancer / tension sensor
feedback input filter time
constant
0
0
Without filter
0.01 to 5 s
Set the primary delay filter for the tension feedback
input value.
Pr.133 setting
Actual set point
600%
+100%
500% (initial setting)
0%
400%
-100%
Pr.363 setting
Input terminal
3
Terminal 2 (0 to 100%) (0 to 5 VDC)
4
Terminal 4 (20 to 100%) (4 to 20 mADC)
5 (initial value)
Terminal 1 (-100 to 100%) (0 to
±
10 VDC)
6
Terminal 6 (FR-A8AZ) (-100 to 100%) (0 to
±
10 VDC)
3 V
30 N
0 V
10 V
100 N
Tension setting using
analog input value
Set point
600%
530%