Tension sensor feedback torque control details
TENSION SENSOR FEEDBACK TORQUE CONTROL
149
6
6.5.2
Winding/unwinding shaft selection
Select whether the target roll is a winding shaft or unwinding shaft.
Winding/unwinding selection (Pr.1230)
• Use
Pr.1230 Winding/unwinding selection
to select whether the target roll is a winding shaft or unwinding shaft.
• The initial diameter of the winding shaft is selected according to whether the operation is winding or unwinding.
6.5.3
Tension feedback setting
Set parameters for tension feedback.
Select the input interface (analog input terminal) used for inputting tension feedback to the inverter.
∗1
The setting range varies depending on the
Pr.1401
setting.
PID set point
• Use a commanded tension value after taper compensation to set the set point for tension feedback. Select the tension
command input method in
Pr.804 Tension / Torque command source selection
.
NOTE
• Refer to
Pr.804
for the taper function.
Tension feedback input selection (Pr.363)
• Use
Pr.363 Dancer / tension sensor feedback input selection
to select the input terminal for tension feedback.
∗1
The input specification in the initial setting is indicated.
Pr.
Name
Initial value
Setting
range
Description
1230
R002
Winding/unwinding selection
0
0
Winding
1
Unwinding
Pr.1230
setting
Winding/unwinding selection
Initial roll diameter
0
Winding
Minimum roll diameter
1
Unwinding
Maximum roll diameter
Pr.
Name
Initial value
Setting
range
Description
363
R102
Dancer / tension sensor
feedback input selection
9999
3
The measured value is input through terminal 2.
4
The measured value is input through terminal 4.
5
The measured value is input through terminal 1.
6
The measured value is input through terminal 6 on the
FR-A8AZ.
9999
No function
1136
R330
Tension sensor feedback
voltage/current bias
0%
0 to 100%
Set the bias voltage (current) in % for analog input.
1137
R331
Tension sensor feedback
bias
0 N
0 to 100 N
Set the tension feedback bias value for analog input.
1138
R332
Tension sensor feedback
voltage/current gain
100%
0 to 100%
Set the gain voltage (current) in % for analog input.
1139
R333
Tension sensor feedback
gain
100 N
0 to 100 N
Set the tension feedback gain value for analog input.
1227
R103
Dancer / tension sensor
feedback input filter time
constant
0
0
Without filter
0.01 to 5 s
Set the primary delay filter for the tension feedback
input value.
Pr.363 setting
Input terminal
3
Terminal 2 (0 to 100%) (0 to 5 VDC)
4
Terminal 4 (20 to 100%) (4 to 20 mA)
5 (initial value)
Terminal 1 (-100 to 100%) (0 to ±10 VDC)
6
Terminal 6 on the FR-A8AZ (-100 to 100%) (0 to ±10 VDC)