Dancer feedback speed control details
72
Dancer signal input selection (Pr.363)
• Use
Pr.363 Dancer / tension sensor feedback input selection
to select the input terminal for the dancer signal
(measured value).
Dancer signal calibration example
• The following parameters are used for calibrating the dancer signal according to the input terminal. The dancer signal
analog input values at both 0% and 100% can be calibrated.
∗1
The initial input range is 20 to 100%.
• In the following example, a potentiometer with the output range of -10 to 10 V is used for inputting the dancer signal to
terminal 1 (input range: -10 to 10 V). The neutral position is defined as 0% for the calibration.
C13 (Pr.917) Terminal 1 bias
(speed)
and
C15 (Pr.918) Terminal 1 gain (speed)
are used for calibration.
• In the following example, a potentiometer with the output range of 1 to 7 V is used for inputting the dancer signal to terminal
2 (input range: 0 to 10 V). The neutral position is defined as 0% for the calibration.
C3 (Pr.902) Terminal 2 frequency
setting bias
and
C4 (Pr.903) Terminal 2 frequency setting gain
are used for calibration.
Pr.363 setting
Input terminal
3
Terminal 2 (0 to 100%) (0 to 5 V)
4
Terminal 4 (20 to 100%) (4 to 20 mA)
5 (initial value)
Terminal 1 (-100 to 100%) (-10 to 10 V)
6
Terminal 6 (FR-A8AZ) (-100 to 100%) (-10 to 10 V)
Input terminal
Calibration parameter
Terminal 2 (0 to 100%)
C3 (Pr.902)
,
C4 (Pr.903)
Terminal 4 (0 to 100%)
C6 (Pr.904)
,
C7 (Pr.905)
Terminal 1 (-100 to 100%)
C13 (Pr.917)
,
C15 (Pr.918)
Terminal 6 (FR-A8AZ) (-100 to 100%)
C31 (Pr.926)
,
C33 (Pr.927)
Potentiometer
-10 to 10 V
Terminal 1 calibration example
100%
-100%
0
C13 (Pr.917)
Analog input value
10 V
C15 (Pr.918)
Calibration example
(initial value)
-10 V
Dancer signal
Potentiometer
1 to 7 V
Terminal 2 calibration example
Calibration example
100%
-100%
Dancer signal
0
1 V
Analog
input value
10 V
7 V
C4 (Pr.903)
4 V
C3 (Pr.902)