Roll to roll dedicated I/O signal
ROLL TO ROLL FUNCTION RELATED PARAMETERS
191
9
9.2.2
Output signal
• To use output signals, assign them to
Pr.190 to Pr.196 (output terminal function selection)
.
Output signal list
List of output signals with validity status by control mode (function)
Pr.190 to Pr.196
setting
Signal name
Description
Refer
to
page
Positive
logic
Negative
logic
14
114
PID lower limit
FDN
Output when the dancer roll position or the roll tension value goes lower
than the limit determined by the setting of
Pr.132 PID lower limit
.
15
115
PID upper limit
FUP
Output when the dancer roll position or the roll tension value goes higher
than the limit determined by the setting of
Pr.131 PID upper limit
.
231
331
Break detection
Y231
Output when the dancer roll position or the roll tension becomes
abnormal due to a break.
232
332
Winding diameter
calculation
completion at start
Y232
Output when the diameter calculation is completed at an operation start.
233
333
Target winding
diameter achieved
Y233
Output when the diameter reaches the setting in
Pr.648 Target winding
diameter
or longer for winding.
Output when the diameter reaches the setting in
Pr.648 Target winding
diameter
or shorter for unwinding.
234
334
Winding/unwinding
completion
Y234
Output when the winding/unwinding length is equal to or more than the
value of determined by the settings of
Pr.1264 Winding length
detection (lower 4 digits)
and
Pr.1346 Winding length detection
(upper 4 digits)
.
235
335
Dancer position /
tension feedback
detection
Y235
Output while the dancer roll position or the roll tension is within a range
determined by the setting of
Pr.423 Dancer / tension sensor feedback
detection level
. This signal is also output when the inverter is at a stop.
,
236
336
Reel change ready
Y236
Output when the commanded line speed reaches the target line speed
while the reel change function is valid.
237
337
Line speed
acceleration
Y237
Output while the commanded line speed increases. The signal can be
input to the terminal to which the Inertia compensation acceleration
(X111) signal of the inverter for the driving shaft is assigned.
,
238
338
Line speed
deceleration
Y238
Output while the commanded line speed decreases. The signal can be
input to the terminal to which the Inertia compensation deceleration
(X112) signal of the inverter for the driving shaft is assigned.
,
239
339
Average current
load detection
Y239
Output when the output current average value reaches or exceeds 50%
of the inverter rated current. (This function is only available for the SND
rating.)
Pr.190 to Pr.196
setting
Signal name
Dancer
feedback
speed
control
Tension
sensor
feedback
speed
control
Tension
sensorless
torque
control
Tension
sensor
feedback
torque
control
Winding
diameter
calculation
Positive
logic
Negative
logic
14
114
PID lower limit
FDN
—
—
15
115
PID upper limit
FUP
—
—
231
331
Break detection
Y231
—
—
232
332
Winding diameter
calculation completion at
start
Y232
—
—
—
—
233
333
Target winding diameter
achieved
Y233
—
—
—
—
234
334
Winding/unwinding
completion
Y234
—
—
—
—
235
335
Dancer position / tension
feedback detection
Y235
—
—
—
236
336
Reel change ready
Y236
—
—
—
237
337
Line speed acceleration
Y237
—
—
—
238
338
Line speed deceleration
Y238
—
—
—
239
339
Average current load
detection
Y239