Monitoring of dedicated functions
ROLL TO ROLL FUNCTION RELATED PARAMETERS
187
9
Setting monitoring reference (Pr.55, Pr.276, Pr.866, Pr.1280, Pr.1281)
Set the full-scale value for outputting the monitor items of output frequency, frequency setting value, and line speed to
terminals FM, CA and AM.
∗1
The value in parentheses is the number of pulses for the high-speed pulse train output (
Pr.291 Pulse train I/O selection
= "10, 11, 20, 21, or
100").
Output frequency (
Pr.55
)
Line speed (
Pr.276
)
Torque (
Pr.866
)
Winding diameter (
Pr.1280
)
Tension command (
Pr.1281
)
Output frequency (
Pr.55
)
Line speed (
Pr.276
)
Torque (
Pr.866
)
Winding diameter (
Pr.1280
)
Tension command (
Pr.1281
)
Output frequency (
Pr.55
)
Line speed (
Pr.276
)
Torque (
Pr.866
)
Winding diameter (
Pr.1280
)
Tension command (
Pr.1281
)
Full-scale value
Full-scale value
Full-scale value
590 Hz
6553.4 m/min
400%
6553 mm
100N
0 Hz
0 m/min
0%
1 mm
0N
Monitor reference setting range for terminal FM
590 Hz
6553.4 m/min
400%
6553 mm
100N
0 Hz
0 m/min
0%
1 mm
0N
590 Hz
6553.4 m/min
400%
6553 mm
100N
0 Hz
0 m/min
0%
1 mm
0N
Pulse speed
(pulses/s)
2400
(55k)
∗1
1440
(50k)
∗1
Monitor setting range for terminal CA
20 mADC
Output current
Monitor setting range for terminal AM
10 VDC
-10 VDC
Output voltage