Dancer feedback speed control details
85
3
3.5.12
Integral control action setting
The manipulated amount for PID integral action can be limited by setting parameters.
The integral control action can be enabled or disabled (the integral term is held) according to the PID control deviation.
Integral control can be disabled by the signal input. (The integral term value is cleared.)
Integral action limit (Pr.135, Pr.136)
• Use
Pr.135 Integral clamp (positive polarity)
or
Pr.136 Integral clamp (negative polarity)
to limit the manipulated
amount for PID integral action.
Integral control action selection (Pr.485)
• The integral control action can be selected according to the PID control deviation.
• Use
Pr.486 to Pr.489
to set the deviation, and use
Pr.485 Integral control activation
to select the action.
• In the holding period, the integral of the deviation is stopped and the integral term is retained as it is. The manipulated
amount is calculated using the kept integral term value.
∗1
The integral of the deviation is valid when "9999" is set in
Pr.488
or
Pr.489
.
Pr.
Name
Initial value
Setting
range
Description
135
R161
Integral clamp (positive
polarity)
9999
0 to 100%
Set the limit level for integral action.
9999
The limit level is 100%.
136
R162
Integral clamp (negative
polarity)
9999
0 to 100%
Set the limit level for integral action (negative polarity).
9999
As set in
Pr.135
.
485
R149
Integral control activation
0
0 to 3
Select the action for integral control.
486
R140
Deviation A
600%
400.1 to 600%
Set the reference deviation for the integral control
action set in
Pr.485
.
9999: Integral control is valid.
487
R141
Deviation B
400%
400 to 599.9%
488
R142
Deviation C1
9999
400.1 to
599.9%
9999
489
R143
Deviation C2
9999
400.1 to
599.9%
9999
1015
A607
Integral stop selection at
limited manipulated amount
0
0
The integral stops when manipulated amount is limited.
1
The integral does not stop when manipulated amount is
limited.
Pr.135 setting
Pr.136 setting
Integral action limit level
(positive polarity)
Integral action limit level
(negative polarity)
9999
9999
100%
100%
9999
0 to 100%
100%
Pr.136
setting
0 to 100%
9999
Pr.135
setting
Pr.135
setting
0 to 100%
0 to 100%
Pr.135
setting
Pr.136
setting
+100%
0%
-100%
Deviation input
Deviation C1
(Pr.488)
Deviation A
(Pr.486)
Deviation C2
(Pr.489)
Deviation B
(Pr.487)
Enabled
Enabled
Enabled
Held
Held
∗1
Held
Enabled
Enabled
Held
Held
Enabled
Held
∗1
Pr.485
="0"
Pr.485
="1"
Pr.485
="2"
Pr.485
="3"