Application examples
209
10
Example setting of parameters
The following shows mechanical specifications and parameter settings required for configuring the system shown as the
application example. The parameter settings are examples for a 7.5 kW motor and the 11 kW inverter used for the winding
roller.
Item
Specification
Item
Specification
Minimum roll diameter
100 mm
Initial roll diameter
calculation
Disabled
Maximum roll diameter
300 mm
Roll diameter storage
Enabled
Gear ratio
1/1.2
Tension command
0 to 300 N
Maximum speed of the
actual line
400 m/min
Tension setting output
Required
Pr.
Parameter name
Initial
value
Setting value
Remarks
Intermediate
roller
Winding
roller
7
Acceleration time
15 s
0 s
8
Deceleration time
15 s
0 s
9
Electronic thermal O/L relay
Inverter
rated
current
0
10
DC injection brake operation
frequency
3 Hz
0.5 Hz
0 Hz
12
DC injection brake operation
voltage
4%
2.5%
52
Operation panel main monitor
selection
0
27
22
Set "22" (Roll diameter) or "27" (Actual line
speed) for monitoring.
Or use any of
Pr.774 to Pr.776
when using the 3-
line monitor screen on the PU.
Other monitor items related to this application and
their setting values are as follows:
26 (Line speed command), 81 (Tension command
after taper compensation), 82 (Winding diameter
compensation torque command), 83 (Inertia
compensation), and 84 (Mechanical loss
compensation).
71
Applied motor
0
30
30: Setting for the Mitsubishi Electric Vector
control dedicated motor SF-V5RU.
73
Analog input selection
1
1
10
10: Terminal 2 input between 0 to 10 V for the line
speed with reversible polarity.
80
Motor capacity
9999
7.5 kW
Set these parameters according to the motor.
81
Number of motor poles
9999
4 (poles)
83
Rated motor voltage
200 V
164 V
84
Rated motor frequency
9999
51 Hz
95
Online auto tuning selection
0
0
2
2: Magnetic flux observer (continuous tuning)
128
PID action selection
0
40
0
129
PID proportional band
100%
9999
100%
130
PID integral time
1 s
9999
1 s
134
PID differential time
9999
9999
9999
158
AM terminal function selection
1
26
1
26 (for intermediate roller): Line speed command
value
180
RL terminal function selection
0
114
114: Tension control selection (X114) signal ON
(Setting "114" is required for tension control.)
181
RM terminal function selection
1
1
109
109: Stored winding diameter clear (X109) signal
ON (Setting "109" clears the stored roll diameter.)
182
RH terminal function selection
2
2
123
123: Stall mode trigger signal (X123) signal ON
(Setting "123" triggers the stall mode.)
184
AU terminal function selection
4
4
111
To use the inertia compensation function, assign
the Inertia compensation acceleration (X111)
signal and the Inertia compensation deceleration
(X112) signal.
189
RES terminal function selection
62
62
112
193
OL terminal function selection
3
237
3
To use the inertia compensation function, assign
the Line speed acceleration (Y237) signal and the
Line speed deceleration (Y238) signal to affected
output terminals on the inverter for the
intermediate roller to output these signal to the
inverter for the winding roller (shaft).
194
FU terminal function selection
4
238
4