Remote RMM-1400 Version 2.0x Configuration Guide
Configuring the Peripheral Management Subsystem: Configuring SiteBus Devices for an Expansion
Peripheral
16-16
Configuring SiteBus Devices for an Expansion Peripheral
The RMB-1 and RMB-2 expansion peripheral units include a four-terminal SiteBus,
where you can connect sensors that transmit data over a single wire. Each of these
“one-wire” SiteBus devices has a unique hexidecimal ID, which is discovered by
RMB. After you connect a SiteBus device and the device has been discovered, you
can configure the device for management by Remote RMM-1400.
To configure a SiteBus device:
1. Power down the RMB peripheral by disconnecting its Ethernet connection to
Remote RMM-1400.
2. Use RMB’s punchdown tool to physically connect the device to a SiteBus
terminal.
Note:
For more information, see section Connecting Wires to RMB Punchdown
Terminals in the
Remote RMM-1400 Installation Guide
.
3. Power up the RMB peripheral by reconnecting its Ethernet connection to Remote
RMM-1400. RMB discovers the newly connected SiteBus device.
4. Obtain the hexidecimal ID for the newly connected SiteBus device:
show sitebus
In the following example, device
28004564AE05A5
has been discovered, but is not
yet managed by Remote RMM-1400.
5. Configure the device with name
temp1
:
config sitebus temp1
In this scenario, you will:
Connect a device to a SiteBus terminal and discover its hexidecimal ID
Configure a SiteBus device for management by Remote RMM-1400
(Dub)>show
(Dub) show>sitebus
ID Periph:Bus State Managed Name
------------------------------------------------------------------------------
28004564AE05A5 1:1 Unmanaged
Name ID State Type Description
-----------------------------------------------------------------------------
(Dub) show>