![Kentrox RMM-1400 Configuration Manual Download Page 117](http://html1.mh-extra.com/html/kentrox/rmm-1400/rmm-1400_configuration-manual_1955455117.webp)
Remote RMM-1400 Version 2.0x Configuration Guide
Configuring Measurements and the Measurement Table: Configuring a Measurement Table Entry for a
Temperature Sensor
13-5
10. (optional) Verify that the measurement table entry has been configured properly:
show meas-table entries ExtTemp1
The command response appears similar to the following:
11. Save the configuration.
Sample Configuration for SiteBus Temperature Sensor
The following is a sample configuration for a measurement table entry for the SiteBus
temperature sensor used with RMB-1 and RMB-2. Adjust the sensor name, NE name,
and other values to fit your specific implementation.
config meas-table entry TempSensor1
config meas-table entry TempSensor1 category Temp Sensor
config meas-table entry TempSensor1 description One Wire Temp
Sensor
config meas-table entry TempSensor1 originator sitebus
Temp/temperatureF
config meas-table entry TempSensor1 report-interval 15
config meas-table entry TempSensor1 band 20 110
config meas-table entry TempSensor1 hysteresis 2
config meas-table entry TempSensor1 maximum 150
config meas-table entry TempSensor1 minimum -10
config meas-table entry TempSensor1 ne-name Test_RMM1400
config meas-table entry TempSensor1 units degrees Fahrenheit
(Dub)>show meas-table entries ExtTemp1
Name - ExtTemp1 (static)
State - offline
Originator - analog 1/4
Description - External temperature sensor
NE Name - sensorUnit
Category - envAlms
Report Interval - 0
Low-Band - 65.
High-Band - 80.
Hysteresis - 0.
Max-Limit - 130.
Min-Limit - -30.
Units - Degrees F
Current Value - 76
Interval Value - 76
Interval Minimum - 76
Interval Maximum - 76
Interval Average - 76
(Dub)>