Remote RMM-1400 Version 2.0x Configuration Guide
Configuring Alarm Entries in the Central Alarm Table: Configuring an Alarm Entry for a Temperature
Sensor
12-6
10. (optional) Verify that the alarm entry has been configured properly:
show alarm-entries name tempSensor
The command response appears similar to the following:
11. Save the configuration.
Configuring Analog Input Values
The values reported by Remote analog inputs often show rapid fluctuations as
compared to the values read from a digital multi-meter.
This is by design and does not
indicate a problem with the Remote. Digital multi-meters utilize sophisticated internal
circuitry to minimize these inherent fluctuations when displaying measurements to the
user. To compensate for these variations, Remote provides two analog input features:
analog averaging and analog adjustment.
Analog Averaging
Users can specify the level at which Remote will average measurement values. The
goal is for a reasonable, steady-state value to measure consistently with both the
Remote and an external meter. Summarized in
Table 12-1
are the valid averaging
values with typical examples of when they may be applied to a measurement.
(Dub)>show alarm-entries name tempSensor
Name - tempSensor
State - normal
Current Message -
Description - Temperature sensor
Nagging Interval - 5
Nagging Level - critical
Trap - enabled
Trap Priority - high
Raw - enabled
Category - envAlms
NE Name - TempSensor
Originator - input 1/1
Alarm Actions:
Severity Trigger Message
------------------------------------------------------------------
critical
high
Temperature above safe thresho
minor
low
Temperature below low threshol
normal
in-band
Temperature in normal range
(Dub)>