Remote RMM-1400 Version 2.0x Configuration Guide
Configuring the Peripheral Management Subsystem: Configuring Alarms for an Expansion Peripheral
16-11
Configuring Alarms for an Expansion Peripheral
To configure alarms for an expansion peripheral:
1. Configure alarm entry
Input5_closed
as a
major
alarm that signals when
discrete input
1/5
goes down:
config alarm-entry Input5_closed event input 1/5 close major Input
5 is closed
2. Configure alarm entry
Input5_open
as a
normal
alarm that signals when discrete
input
1/5
comes up:
config alarm-entry Input5_open event input 1/5 open normal Input 5
is open
3. (optional) Verify that the alarm entries have been configured properly:
show alarm-entries name Input5_closed
The display will look similar to the following for alarm entry
Input5_closed
:
In this scenario, you will:
Configure an alarm entry that signals when a discrete input on RMB is closed
Configure an alarm entry that signals when the discrete input is open
(Dub)>show alarm-entries name Input5_closed
Name - Input5_closed
State - normal
Current Message -
Description -
Nagging Interval - 0
Nagging Level - major
Trap - enabled
Trap Priority - disabled
Raw - disabled
Category -
NE Name -
Originator - input 1/5
Alarm Actions:
Severity Trigger Message
------------------------------------------------------------------
major close Input 5 is closed
(Dub)>