Remote RMM-1400 Version 2.0x Configuration Guide
Configuring Measurements and the Measurement Table: Configuring an Alarm Entry for a Measurement
13-8
10. (optional) Verify that the alarm entry has been configured properly:
show alarm-entries name ExtTemp
The command response appears similar to the following:
11. Save the configuration.
(Dub)>show alarm-entries name ExtTemp
Name - ExtTemp
State - normal
Current Message -
Description - Exterior temperature alarm
Nagging Interval - 0
Nagging Level - major
Trap - enabled
Trap Priority - normal
Raw - disabled
Category - envAlms
NE Name - sensorUnit
Originator - measurement ExtTemp1
Alarm Actions:
Severity Trigger Message
------------------------------------------------------------------
major high $(value)
major low $(value)
normal in-band $(value)
critical input-saturated Input saturated
critical loss-of-signal Signal loss
(Dub)>