Remote RMM-1400 Version 2.0x Configuration Guide
Configuring Measurements and the Measurement Table: Configuring an Alarm Entry for a Measurement
13-6
Configuring an Alarm Entry for a Measurement
To configure the measurement alarm entry:
1. At the main prompt, configure alarm entry
ExtTemp
with description
External
temperature alarm
:
config alarm-entry ExtTemp description External temperature alarm
2. Configure category name
envAlms
:
config alarm-entry ExtTemp category envAlms
3. Configure network element name
sensorUnit
:
config alarm-entry ExtTemp ne-name sensorUnit
4. Enable SNMP trap alarm protocol support with priority
normal
:
config alarm-entry ExtTemp trap enable
config alarm-entry ExtTemp trap priority normal
5. Configure an event for alarm entry
ExtTemp
with the following settings:
Event originator
measurement ExtTemp1
Event trigger
high
Event severity level
major
Alarm event message
$(value)
.
Note:
Keyword
$(value)
is replaced with the current measurement value.
config alarm-entry ExtTemp event measurement ExtTemp1 high major
$(value)
In this scenario, you will:
Configure an alarm entry description and category
Configure the network element name associated with this alarm entry
Configure SNMP trap alarm protocol support
Configure different alarm actions that occur when a measurement is normal,
low, high, falls below the measurable range, or rises above the measurable
range