Remote RMM-1400 Version 2.0x Configuration Guide
Configuring Alarm Entries in the Central Alarm Table: Configuring an Alarm Entry for a Serial Connection
Failure
12-10
Configuring an Alarm Entry for a Serial Connection Failure
To configure an alarm entry for a serial connection failure:
1. At the main prompt, configure description
Serial connection failure
:
config alarm-entry SerConnFail description Serial connection
failure
2. Enable SNMP trap alarm protocol support:
config alarm-entry SerConnFail trap enable
3. Configure an event for alarm entry
SerConnFail
with the following settings:
Event originator
serial 3
Event trigger
conn-failed
Event severity level
major
Alarm event message
The serial connection has failed
.
config alarm-entry SerConnFail event serial 3 conn-failed major
The serial connection has failed
In this scenario, you will:
Configure an alarm entry description
Configure SNMP alarm protocol support
Configure an alarm action that signals that a serial connection failure has
occurred.
Important:
This scenario does not show how to configure the serial port that is
associated with the alarm entry. For information on configuring serial
ports, refer to command
config controller serial
in the
Remote
RMM-1400 Command Reference Guide
.