Remote RMM-1400 Version 2.0x Configuration Guide
Configuring Alarm Entries in the Central Alarm Table: Configuring an Alarm Entry for a Discrete Input
12-8
Configuring an Alarm Entry for a Discrete Input
To configure the open input alarm entry:
1. At the main prompt, configure description
Light switch
:
config alarm-entry input1_1 description Light Switch
2. Enable
trap
alarm protocol support:
config alarm-entry input1_1 trap enable
3. Configure an event for alarm entry
input1_1
with the following settings:
Event originator
input 1/1
Event trigger
open
Event severity level
major
Alarm event message
Light off
.
config alarm-entry input1_1 event input 1/1 open major Light off
4. Configure an event for alarm entry
input1_1
with the following settings:
Event originator
input 1/1
Event trigger
close
Event severity level
major
Alarm event message
Light on
.
config alarm-entry input1_1 event input 1/1 close major Light on
In this scenario, you will:
Configure an alarm entry description
Configure SNMP alarm protocol support
Configure an alarm action that occurs when a light turns off, which opens an
input
Configure an alarm action that occurs when a light turns on, which closes an
input.
Important:
This scenario does not show how to configure the discrete input that is
associated with the alarm entry. For information on configuring
discrete inputs, refer to command
config discrete input
in the
Remote RMM-1400 Command Reference Guide
.