Remote RMM-1400 Version 2.0x Configuration Guide
Configuring Alarm Entries in the Central Alarm Table: Configuring an Alarm Entry for a Temperature
Sensor
12-5
7. Configure an event for alarm entry
tempSensor
with the following settings:
Event originator
analog 1/1
Event trigger
high
Event severity level
critical
Alarm event message
Temperature above safe threshold -
followed by
the actual high value for the alarm entry.
config alarm-entry tempSensor event analog 1/1 high critical
Temperature above safe threshold - $(value)
Note:
Keyword
$(value)
is replaced with the current value of the analog input. If the
event associated with the analog input does not contain an event message
value, no substitution takes place.
8. Configure a second event for alarm entry
tempSensor
with the following settings:
Event originator
analog 1/1
Important:
All events configured for an alarm entry must have the same event
originator.
Event trigger
low
Event severity level
minor
Alarm event message
Temperature below low threshold -
followed by
the actual low value for the alarm entry.
config alarm-entry tempSensor event analog 1/1 low minor
Temperature below low threshold - $(value)
9. Configure a third event for alarm entry
tempSensor
with the following settings:
Event originator
analog 1/1
Event trigger
in-band
Event severity level
normal
Alarm event message
Temperature in normal range
.
config alarm-entry tempSensor event analog 1/1 in-band normal
Temperature in normal range