JPDM-[ ] P28v-S contact input (JS connector) indicates PS problem
Possible Cause
•
The power supply contact is open. The power supply is not operating normally.
•
The power supply contact feedback is not connected to the terminal board JS connector.
•
The power supply contact is not used.
Solution
•
Verify the status of the power supply contact and that the power supply is operating correctly.
•
Verify the connections between the power supply and the JS connector on the terminal board.
•
The JS input is not used. Set
PS28vEnable
to
Disable
.
•
The power supply is used, but the JS contact feedback is not connected. Set
PS28vEnable
to
NoDryCnt
to disable this
alarm, but continue to monitor the 28 V power supply input.
58, 61
Description
JPDM-[ ] P28v-T contact input (JT connector) indicates PS problem
Possible Cause
•
The power supply contact is open. The power supply is not operating normally.
•
The power supply contact feedback is not connected to the terminal board JT connector.
•
The power supply contact is not used.
Solution
•
Verify the status of the power supply contact, and that the power supply is operating correctly.
•
Verify the connections between the power supply and the JT connector on the terminal board.
•
The JT input is not used. Set
PS28vEnable
to
Disable
.
•
The power supply is used, but the JT contact feedback is not connected. Set
PS28vEnable
to
NoDryCnt
to disable this
alarm, but continue to monitor the 28 V power supply input.
PDM Power Distribution Modules
GEH-6855_Vol_II System Guide 325