2.1.4
UCSC Mounting and Installation Requirements
2.1.4.1
UCSC Mounting Requirements
The following are requirements for mounting the UCSC controller:
•
Directly mount the UCSC to the mounting base using the two mounting screws.
•
Vertical mount with unobstructed air flow through fins.
•
Leave a minimal 100 mm (3.94 in) air gap above and below the UCSC.
•
Parallel mount UCSC to UCSC requires a minimal 50 mm (1.97 in) spacing to achieve full temperature rating.
•
The
envelope is 25 mm (0.98 in) from any point on UCSC.
Controllers
GEH-6855_Vol_II System Guide 21
Public Information