10.3
PPDA Specific Alarms
The following alarms are specific to the PPDA I/O pack.
32, 35
Description
JPDS-[ ] P28v-R volt fdbk (JR/PR connector) out of range
Possible Cause
•
The 28 V Power supply input is out of range. It is expected to be within ±5% of 28 V.
•
The 28 V R power supply has not been connected.
•
There could be a power supply problem.
Solution
•
The input is not used. Set
PS28vEnable
to
Disable
.
•
Verify the power supply connections (JR/PR) to the terminal board.
•
Verify that the power supply feedback on the
JPDS/M Inputs
tab in the ToolboxST application is within the expected
tolerance (±5%).
33, 36
Description
JPDS-[ ] P28v-S volt fdbk (JS/PS connector) out of range
Possible Cause
•
The 28 V Power supply input is out of range. It is expected to be within ±5% of 28 V.
•
The 28 V S power supply has not been connected.
•
There could be a power supply problem.
Solution
•
The input is not used. Set
PS28vEnable
to
Disable
.
•
Verify the power supply connections (JS/PS) to the terminal board.
•
Verify that the power supply feedback on the
JPDS/M Inputs
tab in ToolboxST is within the expected tolerance (±5%).
PDM Power Distribution Modules
GEH-6855_Vol_II System Guide 319
Public Information