155, 163
Description
JPDE-[ ] fuse FUA1/FUA2 (JFA connector) is blown.
Possible Cause
•
The FUA1 or FUA2 fuse is blown.
•
The 24/48 V dc input is not connected.
Solution
•
Replace the fuse.
•
Verify the 24/48 V dc input connections to the terminal board.
•
If the 24/48 V dc input is not used, this diagnostic alarm can be disabled by setting the
InputDiagEnab
parameter on the
associated input (
DC_24VFdbkMag
) to
Disabled
.
156, 164
Description
JPDE-[ ] fuse FUB1/FUB2 (JFB connector) is blown.
Possible Cause
•
The FUB1 or FUB2 fuse is blown.
•
The 24/48 V dc input is not connected.
Solution
•
Replace the fuse.
•
Verify 24/48 V dc input connections to the terminal board.
•
If the 24/48 V dc input is not used, this diagnostic alarm can be disabled by setting the
InputDiagEnab
parameter on the
associated input (
DC_24VFdbkMag
) to
Disabled
.
157, 165
Description
JPDE-[ ] fuse FUC1/FUC2 (JFC connector) is blown.
Possible Cause
•
The FUC1 or FUC2 fuse is blown.
•
The 24/48 V dc input is not connected.
Solution
•
Replace the fuse.
•
Verify the 24/48 V dc input connections to the terminal board.
•
If the 24/48 V dc input is not used, this diagnostic alarm can be disabled by setting the
InputDiagEnab
parameter on the
associated input (
DC_24VFdbkMag
) to
Disabled
.
PDM Power Distribution Modules
GEH-6855_Vol_II System Guide 343
Public Information