206 – 207
Description
JPDG ACIn-[ ] [ ]V fdbk (JAC1 connector) out of range
Possible Cause
•
The specified ac input is configured to the wrong nominal voltage value.
•
The ac input voltage is out of tolerance from the nominal voltage value.
•
The ac source voltage is out of range.
•
The ac input is not connected.
Solution
•
Verify that the nominal ac input voltage matches the value configured in the ACFdbkInVoltage.
•
The ac tolerance is set too low. Check that the ACFdbkInTol is set to the proper value.
•
Verify that the ac supply is within the specified parameters.
•
If the ac input is not used, this diagnostic alarm can be disabled by setting the InputDiagEnab parameter on the associated
input (AC_Fdbk#_Volt) to
Disabled
.
208
Description
JPDG DC 24V Voltage fdbk mag (JPS1/JPS2 connector) out of range
Possible Cause
•
The 24/48 V dc input is less than the DC_24v_Trig_Volt.
•
The DC_24v_Trig_Volt is set too high.
•
The 24/48 V dc source voltage is out of range.
•
The 24/48 V dc input is not connected.
Solution
•
Verify that the DC_24v_Trig_Volt is set correctly.
•
Check the connections to the specified connector.
•
Check the grounding of the dc input signals.
•
If 24/48 V dc input is not used, this diagnostic alarm can be disabled by setting the InputDiagEnab parameter on the
associated input (DC_24VFdbkMag) to
Disabled
.
358
GEH-6855_Vol_II
GEH-6855_Vol_II Mark VIeS Functional Safety Systems Volume II
Public Information