284
Description
Firmware error - Internal process failed
Possible Cause
Runtime or hardware malfunction (runtime process failed)
Solution
•
Reload the firmware and application, and restart the controller and/or I/O module.
•
Re-download the baseload and the firmware.
•
If this does not work, replace the I/O module or controller.
285
Description
Unexpected reboot occurred - hardware fault
Possible Cause
•
Runtime or hardware malfunction
•
Runtime process stalled
Note
This diagnostic alarm is detected on a processor startup after the processor or hardware has malfunctioned and caused
a processor to reboot. Therefore, the diagnostic alarm timestamp may be delayed from when the actual fault occurred.
Solution
•
Reload firmware and application and restart.
•
If the problem persists, replace the processor module.
292
Description
Application Error - application overrunning the frame
Possible Cause
Application cannot start within frame.
Solution
Check application loading and reduce the amount of application code or frequency of execution. Build
application and download to all controllers.
Common I/O Module Functionality
GEH-6855_Vol_II System Guide 461
Public Information