121, 130
Description
JPDF-[ ] fuse FU75 or FU76 (J7Z connector) is blown or SW7Z switched OFF.
Possible Cause
•
The SW7Z is turned off and
FuseDiag
is enabled.
•
The FU75 or FU76 fuse is blown.
•
The 125 V dc input is not connected.
Solution
•
If the switch is turned off (output is not used), disable the diagnostic by setting
FuseDiag
to
Disable
.
•
If the output is used, verify that the switch is turned on.
•
Replace the fuse.
•
Verify the 125 V dc input connections to the terminal board.
•
If the 125 V dc input is not used, this diagnostic alarm can be disabled by setting the
InputDiagEnab
parameter on the
associated input (
DC_125VFdbkMag
) to
Disabled
.
122, 131
Description
JPDF-[ ] fuse FU81 or FU82 (J8A connector) is blown.
Possible Cause
•
The FU81 or FU82 fuse is blown.
•
The 125 V dc input is not connected.
Solution
•
Replace the fuse.
•
Verify the 125 V dc input connections to the terminal board.
•
If the 125 V dc input is not used, this diagnostic alarm can be disabled by setting the
InputDiagEnab
parameter on the
associated input (
DC_125VFdbkMag
) to
Disabled
.