486
Description
Auto-Reconfiguration server installation is incomplete
Possible Cause
•
A download from the ToolboxST application to an I/O pack and/or the Auto-Reconfiguration server has failed
•
Not all of the I/O packs were selected for download
Solution
Perform a scan and download using the ToolboxST application.
487
Description
Auto-Reconfiguration server failed scanning or downloading an I/O pack
Possible Cause
At least one I/O pack is in an unexpected state that the Auto-Reconfiguration server is unable to handle
Solution
•
Cycle power on the I/O pack.
•
Perform a scan and download using the ToolboxST application.
•
Replace the I/O pack.
488
Description
EGD Error - Could not configure consumed exchanges from one or more Producers
Possible Cause
•
Producer EGD Page(s) configured incorrectly
•
Producer(s) powered down
•
Network connectivity intermittent or severed
•
Internal Firmware failure
Solution
•
Rectify configuration error. Compress all pages and download application to Producer.
•
Ensure each Producer is powered on and in the Controlling state.
•
Refer to the Network Troubleshooting guide for possible solutions.
•
Replace the Consumer and/or Producer hardware.