48
Description
Internal data transfer error - Expected ID [ ] Read ErrCntr/ID [ ]
Possible Cause
There is an I/O pack failure or software process conflict that may be cleared by a hard reset.
Solution
•
Cycle power on the I/O pack.
•
Replace the I/O pack.
49
Description
Internal hardware failure - Status [ ]
Possible Cause
An I/O pack has failed.
Solution
Replace the I/O pack.
50
Description
Channel [ ] DC Isolation Test Failure
Possible Cause
The I/O pack failed to auto-calibrate when powered on.
Solution
Replace the I/O pack.
51
Description
I/O pack processor failure - Status [ ]
Possible Cause
The I/O pack failed.
Solution
Replace the I/O pack.
52-64
Description
TVBA Analog Input [ ] Open Circuit ([ ] Volts)
Possible Cause
An open circuit has been detected on the terminal board based on the sensor type.
Solution
•
Check the wiring between the terminal board and the sensor.
•
Check the sensor for proper operation.
•
Replace the terminal board.
272
GEH-6855_Vol_II
GEH-6855_Vol_II Mark VIeS Functional Safety Systems Volume II
Public Information