4.1.4
Specifications
Item
YAIC Specification
Number of Channels
12 channels per terminal board (10 AI, 2 AO)
AI Types Supported
Inputs 1 to 8: ±5 V dc, ±10 V dc, or 4–20 mA
Inputs 9 to 10: 4–20 mA or ±1 mA
Input Converter Resolution
16-bit ADC
I/O Scan Time
Supported Controller I/O Scan rates: 10 ms, 40 ms, 80 ms, 160 ms
Input Accuracy
0.1% of full scale over the full operating temperature range.
Noise Suppression on Inputs
The 10 circuits have hardware filter with single pole down break at 500 rad/s. A software filter,
using a two pole low pass filter, is configurable for: 0.75 Hz, 1.5 Hz, 3 Hz, 6 Hz, 12 Hz
Common Mode Rejection
AC CMR 60 dB at 60 Hz, with up to ±5 V common mode voltage.
DC CMR 80 dB with -5 to +7 peak V common mode voltage
Common Mode Voltage Range
±5 V (±2 V CMR for the ±10 V inputs)
Output Converter
14-bit D/A converter with 0.5% accuracy
Output Load
800 Ω max for 0-20 mA output
Output Accuracy
±0.5% of full measurement range
Power Consumption
5.3 watts typical, 6.2 watts worst case
Compressor Stall Detection
Not supported
Size
8.26 cm high x 4.19 cm wide x 12.1 cm deep (3.25 in x 1.65 in x 4.78 in)
Ambient Rating for Enclosure Design
-40 to 70°C (-40 to 158 °F)
Technology
Surface mount
Note
For further details, refer to the
Mark VIeS Functional Safety Analog I/O Module Summary Sheet
(GEI-100866).
96
GEH-6855_Vol_II
GEH-6855_Vol_II Mark VIeS Functional Safety Systems Volume II
Public Information