Description
Input Src Mismatch on JPDF-[ ]: AC src detected at input instead DC.
Possible Cause
•
The ac voltage has been detected at the 125 V dc input.
Solution
•
Verify the 125 V dc input connections. Use a DVM to verify dc voltage on the input connections.
•
Verify that the positive and negative inputs to the 125 V dc bus are connected to the proper terminals. Refer to the JPDF
help documentation.
172
Description
JPDC-DC 125V fdbk mag (JD1/JZ2 connector) out of range.
Possible Cause
•
The 125 V dc input is less than
DC_125v_Trig_Volt
.
•
DC_125v_Trig_Volt
is set too high.
•
The 125 V dc source voltage is out of range.
•
The 125 V dc input is not connected.
Solution
•
Verify that
DC_125v_Trig_Volt
is set correctly.
•
If fed from the dc battery input, check the connections to JD1 and TB1.
•
If fed from DACA, check the connections to JZ2.
•
Verify the grounding of dc input signals. Refer to the JPDC help documentation.
•
If the 125 V dc input is not used, this diagnostic alarm can be disabled by setting the
InputDiagEnab
parameter on the
associated input (
DC_125VFdbkMag
) to
Disabled
.