292
Description
Application Error - application overrunning the frame
Possible Cause
Application cannot start within frame.
Solution
Check application loading and reduce the amount of application code or frequency of execution. Build
application and download to all controllers.
294
Description
Controller CPU overtemperature, Temp [ ] °C, Threshold [ ] °C
Possible Cause
•
Excessive ambient temperature
•
Hardware malfunction
•
Fan loss
Solution
•
Check the fan (if applicable), the ambient temperature, and for the presence of dust.
•
Replace the controller.
300
Description
Application Code Load Failure
Possible Cause
During commissioning/maintenance:
•
Invalid application configuration
During normal operation:
•
Firmware or hardware malfunction
Solution
•
Rebuild and download the application to all controllers.
•
Reload firmware and application.
•
If problem persists, replace the controller.
Controllers
GEH-6855_Vol_II System Guide 47
Public Information