52, 55
Description
JPDM-[ ] P28v-T volt fdbk (JT/PT connector) out of range
Possible Cause
•
The 28 V power supply input is out of range. It is expected to be within ±5% of 28 V.
•
The 28 V T power supply has not been connected.
•
There could be a power supply problem.
Solution
•
The input is not used. Set
PS28vEnable
to
Disable
.
•
Verify the power supply connections (JT/PT) to the terminal board.
•
Verify that the power supply feedback on the
JPDS/M Inputs
tab in the ToolboxST application is within the expected
tolerance (±5%).
56, 59
Description
JPDM-[ ] P28v-R contact input (JR connector) indicates PS problem
Possible Cause
•
The power supply contact is open. The power supply is not operating normally.
•
The power supply contact feedback is not connected to the terminal board JR connector.
•
The power supply contact is not used.
Solution
•
Verify the status of the power supply contact, and that the power supply is operating correctly.
•
Verify the connections between the power supply and the JR connector on the terminal board.
•
The JR input is not used. Set
PS28vEnable
to
Disable
.
•
The power supply is used, but the JR contact feedback is not connected. Set
PS28vEnable
to
NoDryCnt
to disable this
alarm, but continue to monitor the 28 V power supply input.
324
GEH-6855_Vol_II
GEH-6855_Vol_II Mark VIeS Functional Safety Systems Volume II
Public Information