117, 126
Description
JPDF-[ ] fuse FU1S or FU2S (J1S connector) is blown or SW1S switched OFF
Possible Cause
•
The SW1R is turned off and
FuseDiag
is enabled.
•
The FU1S or FU2S fuse is blown.
•
The 125 V dc input is not connected.
Solution
•
If the switch is turned off (output is not used), disable the diagnostic by setting
FuseDiag
to
Disable
.
•
If the output is used, verify that the switch is turned on.
•
Replace the fuse.
•
Verify the 125 V dc input connections to the terminal board.
118, 127
Description
JPDF-[ ] fuse FU1T or FU2T (J1T connector) is blown or SW1T switched OFF
Possible Cause
•
The SW1R is turned off and
FuseDiag
is enabled.
•
The FU1T or FU2T fuse is blown.
•
The 125 V dc input is not connected.
Solution
•
If the switch is turned off (output is not used), disable the diagnostic by setting
FuseDiag
to
Disable
.
•
If the output is used, verify that the switch is turned on.
•
Replace the fuse.
•
Verify the 125 V dc input connections to the terminal board.
•
If the 125 V dc input is not used, this diagnostic alarm can be disabled by setting the
InputDiagEnab
parameter on the
associated input (
DC_125VFdbkMag
) to
Disabled
.
334
GEH-6855_Vol_II
GEH-6855_Vol_II Mark VIeS Functional Safety Systems Volume II
Public Information