92-95
Description
JPDB-[ ] AC In-[ ] [ ]V fdbk (J1 connector) out of range
Possible Cause
•
The specified ac input is configured to the wrong nominal voltage value.
•
The ac input voltage is out of tolerance from the nominal voltage value.
•
The ac source voltage is out of range.
•
The ac input is not connected.
Solution
•
Verify that the nominal ac input voltage matches the value configured in
ACFdbkInVoltage
.
•
The ac tolerance is set too low. Check that
ACFdbkInTol
is set to the proper value.
•
Verify that the ac supply is within the specified parameters (Refer to the JPDB help documentation.)
•
If the ac input is not used, this diagnostic alarm can be disabled by setting the
InputDiagEnab
parameter on the
associated input (
AC_Fdbk#_Volt
) to
Disabled
.
96-101, 104-109
Description
JPDB-[ ] fuse FU[ ] is blown or SW[ ] switched OFF
Possible Cause
•
The specified switch is turned off and
FuseDiag
is enabled.
•
The specified fuse is blown.
•
The ac input is not connected.
Solution
•
If the switch is turned off (the output is not used), disable the diagnostic by setting
FuseDiag
to
Disable.
•
If the output is used, verify that the switch is turned on.
•
Replace the fuse.
•
Verify the ac input connections to the terminal board.
•
If the ac input is not used, this diagnostic alarm can be disabled by setting the
InputDiagEnab
parameter on the
associated input (
AC_Fdbk#_Volt
) to
Disabled
.
PDM Power Distribution Modules
GEH-6855_Vol_II System Guide 331
Public Information