![background image](http://html.mh-extra.com/html/ge/mark-vies/mark-vies_system-manual_123057119.webp)
5.2
Configuration
5.2.1
Parameters
Parameter
Description
Choices
ContactInput
Mark a specific contact input as Used or Unused.
Used, Unused
SignalInvert
Inversion makes signal true if contact is open
Normal, Invert
SeqOfEvents
Record contact transitions in sequence of events
Enable, Disable
DiagVoteEnab
Enable voting disagreement diagnostic
Enable, Disable
Signal Filter
Contact input filter in milliseconds
Zero, Ten, Twenty, Fifty, Hundred
5.2.2
Inputs
Input
Direction
Type
Contact01
Input
BOOL
↓
↓
↓
Contact24
Input
BOOL
5.2.3
Variables
Note
The following variable names are displayed differently depending on redundancy of I/O pack (R, S, or T).
Variable
Description
Direction
Type
L3DIAG_YDIA_x
I/O diagnostic indication, where x is R, S, or T
Input
BOOL
LINK_OK_YDIA_x
I/O link okay indication, where x is R, S, or T
BOOL
ATTN_YDIA_x
I/O attention indication, where x is R, S, or T
BOOL
IOPackTmpr_x
I/O pack temperature, where x is R, S, or T
REAL
PS18V_YDIA_x
I/O 18 V power supply indication, where x is R, S, or
T
BOOL
PS28V_YDIA_x
I/O 28 V power supply indication, where x is R, S, or
T
BOOL
YDIA Discrete Input Modules