30
Description
Firmware/Configuration Incompatibility Error;Firmware: [ ] Config: [ ]
Possible Cause
I/O pack or module configuration files are incompatible with the firmware. Files have wrong revision.
Solution
•
Confirm the correct installation of the ToolboxST application.
•
Verify that each I/O pack or module is upgraded to the latest version by right-clicking each I/O pack or module and
selecting Upgrade.
•
Rebuild the application and download the firmware and the application code to the affected I/O pack or module.
31
Note
This alarm is obsolete.
Description
Firmware/IO Configuration Incompatibile;Firmware: [ ] IO Config: [ ]
Possible Cause
•
I/O pack or module configuration files are incompatible with the firmware.
•
The files have the wrong revision.
Solution
•
Confirm the correct installation of the ToolboxST application.
•
Verify that each I/O pack or module is upgraded to the latest version by right-clicking each I/O module and selecting
Upgrade.
•
Rebuild the application, and download the firmware and application code to the affected I/O pack or module.
256
Description
[ ]V Pwr supply voltage is low
Possible Cause
Input voltage dropped below 18 V. I/O pack or module input power is required to be within range 28 V
±5%. I/O pack or module operation will be compromised or may stop completely.
Solution
•
If PPDA is available to monitor control cabinet power, check the I/O pack or module for active alarms.
•
Check the I/O pack or module power within the control cabinet; begin with power supplies and work toward the affected
I/O pack or module.