101
Description
I/O pack internal reference voltage out of limits
Possible Cause
The calibration reference voltage for the analog inputs is more than ±5% from the expected value,
indicating a hardware failure.
Solution
•
Check the I/O pack ground quality through mounting bolts.
•
Cycle power to the I/O pack.
•
Replace the I/O pack.
102
Description
I/O pack internal null voltage out of limits
Possible Cause
The calibration Null voltage for the analog inputs is more than ±5% from the expected value, indicating a
hardware failure.
Solution
•
Check the I/O pack ground quality through mounting bolts.
•
Cycle power to the I/O pack.
•
Replace the I/O pack.
128
Description
Logic Signal [ ] Voting Mismatch
Possible Cause
N/A
Solution
N/A
224-235
Description
Input Signal [ ] Voting Mismatch, Local=[ ], Voted=[ ]
Possible Cause
•
Voter disagreement between the R, S and T I/O packs
•
I/O pack is not seated correctly on the terminal board.
Solution
•
Adjust the parameter
TMR_DiffLimt
or correct the cause of the difference.
•
Re-seat the I/O pack to the terminal board.
•
Replace the I/O pack.
YAIC Analog I/O Modules
GEH-6855_Vol_II System Guide 105
Public Information