Description
PPDA Invalid Combination: More than one JPDF Connected to JPDC board.
Possible Cause
The PPDA allows only one JPDF board to be connected to a JPDC as part of the Power Distribution
module. The PPDA has detected more than one JPDF boards connected through ribbon cables to the PDM.
Solution
•
Verify that only one JPDF terminal board is connected to the PDM through ribbon cables.
•
Reboot the PPDA after the hardware connections are corrected.
193
Description
PPDA Invalid Combination: More than one JPDB Connected to JPDC board.
Possible Cause
The PPDA allows only one JPDB board to be connected to a JPDC as part of the Power Distribution
module. The PPDA has detected more than one JPDB boards connected through ribbon cables to the PDM.
Solution
•
Verify that only one JPDB terminal board is connected to the PDM through ribbon cables.
•
Reboot the PPDA after the hardware connections are corrected.
194
Description
PPDA Invalid Combination: JPDC and JPDM boards present Together.
Possible Cause
The PPDA does not allow JPDC and JPDM terminal boards to be mixed. The PPDA has detected both
JPDC and JPDM terminal boards connected through ribbon cables to the PDM.
Solution
•
Verify that there are only JPDC or JPDM boards present, but not both.
•
Verify that the ToolboxST configuration matches the hardware configuration.
•
Reboot the PPDA once the hardware connections have been corrected.