280
Description
Platform hardware does not match configuration
Possible Cause
•
During commissioning or maintenance, the platform type identified in the application configuration does not match
actual hardware
•
During normal operation, there is a hardware failure
Solution
•
From the
General
tab, select
General Properties
, and
Platform
and fix the platform type.
•
Rebuild and download the application.
•
If the problem persists, replace the I/O pack or module.
281
Description
Firmware Load Error - FPGA not programmed due to platform errors
Possible Cause
File downloaded to configure the Field Programmable Gate Array (FPGA) not successfully applied
Solution
•
Verify that all connectors are aligned properly and fully seated.
•
Check the firmware version for compatibility with platform. If it is correct, replace the I/O pack or module.
282
Description
Firmware Load Error - application independent processes failed to initialize
Possible Cause
Runtime malfunction. An application-independent firmware process could not be started successfully.
Solution
•
Reload firmware and application and restart.
•
Controller: If the failure persists, remove the Compact Flash module and reprogram the boot loader using the ToolboxST
configuration. Download using the Device | Download | Controller setup | Format Flash selection. After reinstalling the
flash module and restarting, reload the firmware and application.
•
Replace the module.
•
I/O pack or module: Re-download the base load.
283
Description
Firmware error - Internal process crashed
Possible Cause
Runtime or hardware malfunction (runtime process failed)
Solution
•
Reload firmware and application and restart.
•
Re-download the baseload and the firmware.
460
GEH-6855_Vol_II
GEH-6855_Vol_II Mark VIeS Functional Safety Systems Volume II
Public Information