504
Description
Unauthorized executable was detected and terminated
Possible Cause
When in Secure mode, the controller only permits authorized executables. An unauthorized executable
has been detected and dismissed.
Solution
•
Inspect the syslog/error log messages
•
Rebuild and download the baseload, firmware, and application to the controller.
•
Re-install the ControlST application, then rebuild and download the baseload, firmware, and application to the controller.
505
Description
R network shared I/O module inputs unhealthy
Possible Cause
•
I/O module restarting or restarted
•
I/O module application/configuration missing
•
Application/configuration does not match in I/O module and controller
•
Failed Ethernet connection between I/O module and controller
•
Ethernet cable inserted into wrong connector on I/O module
Note
When using the Shared IONet feature, this alarm is generated if there is a problem with receiving inputs from any
shared I/O module on the R IONet. Refer to
Mark Controllers Shared IONet User Guide
(GEH-6812).
Solution
•
Rebuild and download application/parameters to all controllers and I/O modules.
•
Reload firmware and parameters to the affected I/O module.
•
Reload firmware and application to all controllers.
•
If the problem persists, replace the affected I/O module, then replace the controller.
66
GEH-6855_Vol_II