2402
Description
EtherCAT linebreak detected between devices [ ] and [ ]
Possible Cause
•
An Ethernet cable is disconnected or damaged
•
EtherCAT device(s) is unplugged or without power
Solution
•
Reconnect Ethernet cables.
•
Verify all Ethernet LINK lights are lit.
•
Verify all EtherCAT devices are powered.
2404
Description
EtherCAT limit for lost frames has been exceeded
Possible Cause
•
A device or network component is corrupting the EtherCAT frame
•
An Ethernet cable is damaged
Solution
Use Controller Advanced Diagnostic tool to determine where network issues are located in the device topology.
2405
Description
EtherCAT device disconnected
Possible Cause
•
EtherCAT device(s) is unplugged or without power
•
An Ethernet cable is disconnected or damaged
Solution
•
Ensure all devices are connected and powered.
•
Verify all Ethernet LINK lights are lit.
2406
Description
EtherCAT device in unexpected state
Possible Cause
EtherCAT device(s) have invalid configuration or have experienced a watchdog event.
Solution
Check the EtherCAT device configuration in the ENI file and EtherCAT Configuration Tool.
2407
Description
EtherCAT Master in unexpected state
Possible Cause
Bus does not match ENI file.
Solution
Download a new ENI file or plug in all devices.
82
GEH-6855_Vol_II
GEH-6855_Vol_II Mark VIeS Functional Safety Systems Volume II