1000-2024
Description
Inputs unhealthy on IO Module [ ] IONet [ ] - Minor Signature Mismatch
Possible Cause
Application/configuration does not match in the I/O pack and controller.
Solution
•
Rebuild and download application/parameters to all controllers and I/O packs.
•
Reload firmware and parameters to the affected I/O pack.
•
Reload firmware and application to all controllers.
•
If problem persists, replace affected I/O pack, then replace controller.
1000-2024
Description
Inputs unhealthy on IO Module [ ], R Pack IONet [ ] - Timestamp Mismatch
Possible Cause
Application/configuration does not match in the I/O pack and controller.
Solution
•
Rebuild and download application/parameters to all controllers and I/O packs.
•
Reload firmware and parameters to the affected I/O pack.
•
Reload firmware and application to all controllers.
•
If problem persists, replace affected I/O pack, then replace controller.
1000-2024
Description
Inputs unhealthy on IO Module [ ], S Pack IONet [ ] - Timestamp Mismatch
Possible Cause
Application/configuration does not match in the I/O pack and controller.
Solution
•
Rebuild and download application/parameters to all controllers and I/O packs.
•
Reload firmware and parameters to the affected I/O pack.
•
Reload firmware and application to all controllers.
•
If problem persists, replace affected I/O pack, then replace controller.