10.2.8.3
JPDS Contact/Fuse
Variable**
Description
Direction
Type
DryCntStat_x_y
Pbus x dry contact status (connector Jx)
Input
BOOL
AuxFuseStat_x_y
Pbus x fuse status (connector JAx)
Input
BOOL
** x = R, S, T and y = 1, 2
10.2.8.4
JPDG Inputs
Parameter
Description
Choices
InputDiagEnable
DC or AC volt diagnostics enable
Applicable only to DC_24VFdbkMag, AC_Fdbk1_Volt_#
Enable, Disable
PS28vEnable
PS 28 V feedback enable;
Enable – Enables feedback
Disable – Disables feedback and diagnostics
NoDryCnt – Enables feedback, but disables dry contact
diagnostics
Applicable only to PS28vStat
Enable, Disable, NoDryCnt
DC_24v_Trig_Volt
DC 24 V fault trigger voltage
Applicable only to DC_24VFdbkMag
10 to 60
Gnd_Mag_Trig_Volt
Ground magnitude fault trigger voltage
Applicable only to DC_24VGnd_FdbkMag
1 to 30
ACFdbkInVoltage
AC feedback input voltage
Applicable only to AC_Fdbk1_Volt_#
100 to 250 V
ACFdbkInTol
AC feedback tolerance
Applicable only to AC_Fdbk1_Volt_#
0pct, 5pct, 10pct, 20pct
Variable
Description
Direction
Type
PS28vStat
Main JPDG - PS 28 V feedback from Pbus R input
AnalogInput
REAL
DC_24VFdbkMag
JPDG - DC 24V/48 V magnitude
AnalogInput
REAL
DC_24VGnd_FdbkMag
JPDG - ground feedback magnitude
AnalogInput
REAL
AC_Fdbk1_Volt_1
Main JPDG - AC 115 to 250 V feedback input voltage
AnalogInput
REAL
AC_Fdbk1_Volt_2
Main JPDG - AC 115 to 250 V feedback input voltage
AnalogInput
REAL
316
GEH-6855_Vol_II
GEH-6855_Vol_II Mark VIeS Functional Safety Systems Volume II
Public Information