8.3.4.9
Gap 4-8
[ ] = defaults
†
is only valid with YVIBS1B
Name
Direction
Data
Type
Description
VIB_Type
Scale
Scale_Off
TMR_
DiffLimit
GAP4_VIB4
AnalogIn-
put
REAL
Average Air Gap (for Prox) or DC
volts(for others),DC component of
input#4
Type of vibration
probe, group 1
†
CDM_BN_ChgAmp,
†
CDM_PCB_
ChgAmp,
PosProx,
[Unused],
VibLMAccel,
VibProx,
VibProx-KPH1,
VibProx-KPH2,
VibSeismic,
VibVelomitor
Volts/-
mil or
Volt-
s/ips
[0.2]
0 to 2
Scale
offset for
Prox
position
only, in
mils
[0]
0 to 90
Difference
Limit for Voted
TMR Inputs in
Volts or Mils
[2]
-100 to 100
↓
↓
↓
↓
GAP8_VIB8
AnalogIn-
put
REAL
Average Air Gap (for Prox) or DC
volts(for others),DC component of
input#8
GnBiasOvr-
ide
Snsr_Offset
Gain
SysLim1E-
nabl
SysLim1-
Latch
SysLim1Type
SysLimit1
Gain Bias
Override
[Disable],
Enable
Amount of bias voltage
(dc) to remove from
input signal used to
max. A/Ds signal range
used only when
GnBiasOvride is
enabled
[10]
±13.5
Resolution of
input signal
(net gain
unchanged),
select based
on expected
range, use
only if
GnBiasOvride
is enabled
[1x], 2x, 4x, 8x
Enable System
Limit 1
[Disable],
Enable
Latch the
alarm
[Latch],
NotLatch
System Limit 1
Check Type
[ >= ] , <=
System Limit 1 – GAP in
negative volts
(Velomitor) or positive
mils (Prox)
[90]
-100 to 100
SysLim2Enabl
SysLim2Latch
SysLim2Type
SysLimit2
CDM_Probe_Gain
CDM_Amp_Gain
Enable System
Limit 2
[Disable],
Enable
Latch the
alarm
[Latch],
NotLatch
System Limit 2
Check Type
[ >= ] , <=
System
Limit 2 –
GAP in
negative
volts
(Velomitor)
or positive
mils (Prox)
[10]
-100 to 100
PCB Probe Gain,
pico-coulombs per
psi
[17]
1 to 100
PCB Charge amplifier Gain, millivolts per
pico-coulomb
[10]
1 to 100
YVIB Vibration Monitor Modules
GEH-6855_Vol_II System Guide 267
Public Information